Beschreibung
Technical Specification | SmartPS-100A-SC | SmartPS-80A-T0 | DDSU666-H | DTSU666-H |
General Specification | ||||
Dimensions (HxWxD) | 100 x36 ×65.5 mm (3.9 x1.4 x26 in) |
100 ×72 ×80 mm (3.9 x2.8 x3.1 in.) |
100 ×36 x65.5 mm (3.9 x 1.4 x 2.6 in.) |
100 x72 ×65.5 mm (3.9 x2.8 x2.6 in.) |
Mounting type | DIN35 Rail | |||
Weight (including cables) | 1.2 kg | <0.5 kg | 1.2kg (2.6Ib) | .5 kg (3.3 lb) |
Power Supply | ||||
Power grid type | 1P2W | 3P3W/3P4W | 1P2W | 3P3W/3P4W |
nput voltage(phase voltage | 176-288VAC | 90-500VAC | 176V AC-288VAC | |
Power consumption | ≤0.8 W | ≤1.5W | ≤0.8 W | ≤1W |
Measurement Range | ||||
Line voltage | / | 90-1000 V AC(>500 with external PT ‚) |
/ | 304V AC-499V AC |
Phase voltage | 176-288V AC | 52-577VAC | 176V AC-288V AC | |
Current | 0-100 A | 0-80 A(>80 with external CT2) |
0-100 A | 0-100 A |
Measurement Accuracy | ||||
Current/Noltage | ±0.5% | |||
Power/Energy | ±1% | |||
Frequency | ±0.01 Hz | |||
Communication | ||||
Interface | RS485 | |||
Baud rate | 4800/9600/19200/115200 (9600 bps by defaul) | 9,600 bps | ||
Communication protocol | Modbus-RTU | |||
Environment | ||||
Operating temperature range | -25℃ to +60℃ | |||
Storage temperature range | -40℃ to+70℃ | |||
Operating humidity | 5% RH-95% RH (non-condensing) |